Wind and Structures
Volume 31, Number 6, 2020, pages 509-522
DOI: 10.12989/was.2020.31.6.509
Stability behavior of the transmission line system under incremental dynamic wind load
Hadi Sarmasti, Karim Abedi and Mohammad Reza Chenaghlou
Abstract
Wind load is the principal cause for a large number of the collapse of transmission lines around the world. The
transmission line is traditionally designed for wind load according to a linear equivalent method, in which dynamic effects of
wind are not appropriately included. Therefore, in the present study, incremental dynamic analysis is utilized to investigate the
stability behavior of a 400 kV transmission line under wind load. In that case, the effects of vibration of cables and aerodynamic
damping of cables were considered on the stability behavior of the transmission line. Superposition of the harmonic waves
method was used to calculate the wind load. The corresponding wind speed to the beginning of the transmission line collapse
was determined by incremental dynamic analysis. Also, the effect of the yawed wind was studied to determine the critical attack
angle by the incremental dynamic method. The results show the collapse mechanisms of the transmission line and the maximum
supportable wind speed, which is predicted 6m/s less than the design wind speed of the studied transmission line. Based on the
numerical modeling results, a retrofitting method has been proposed to prevent failure of the tower members under design wind
speed.
Key Words
collapse of transmission tower; wind load; stability analysis; performance of transmission line; dynamic response; incremental dynamic analysis