Steel and Composite Structures
Volume 43, Number 2, 2022, pages 153-164
DOI: 10.12989/scs.2022.43.2.153
Seismic retrofit system made of viscoelastic polymer composite material and thin steel plates
Mohammad Seddiq Eskandari Nasab, Seungho Chun and Jinkoo Kim
Abstract
In this study, a series of cyclic loading tests were performed on viscoelastic dampers (VED) composed of
viscoelastic polymer composite material and thin steel plates to observe the variation of the mechanical properties under
different loading conditions. A mathematical model was developed based on the Kelvin–Voigt and Bouc–Wen models to
formulate the nonlinear force-displacement relationship of the viscoelastic damper. The accuracy of the proposed mathematical
model was verified using the data obtained from the tests. The mathematical model was applied to analyze a reinforced concrete
framed structure retrofitted with viscoelastic dampers. Nonlinear dynamic analysis results showed that the average maximum
inter-story drift ratios of the retrofitted structure met the target limit state after installing the VED. In addition, both the
maximum and residual displacements were significantly reduced after the installation of the VED.
Key Words
cyclic loading test; energy dissipation devices; seismic retrofit; viscoelastic damper
Address
Mohammad Seddiq Eskandari Nasab, Seungho Chun and Jinkoo Kim:Deptartment of Global Smart City, Sungkyunkwan University, Suwon, Republic of Korea